Specifications
Steam Requirements
Specs
For use with low pressure steam; 15 psi or less; steam supply and condensate return pipe connections to unit are 1½" FNPT; condensate trap is an integral part of the unit; must be connected to the site supply by a licensed steam-fitter/pipe-fitter; steam pressure reducing valves not included
Fluid Distribution
2nd Circuit
Heat transfer fluid circuit, 2" hose and Kamlock connections
Reservoir
On-board "open-vented" glycol reservoir; external connection for an optional external extended reservoir; a selector valve is used to select either the on-board reservoir or the external reservoir
Pump
Specs
2HP, 28SFLA, 13FLA
50 - 75 US GPM
Electrical
System Requirements
230V, 1 Ph, 60Hz, 30A
Control Circuitry
24V
Heat Exchanger
Type
304 copper-brazed stainless steel plates (20 plates)
Fluid
Water / steam (hot side); 50.0% Prop.glycol (cold side)
Mass Flow Rate
1036 b/h (hot side); 25120 b/h (cold side)
Fluid Condensed / Vaporized
1036 b/h (hot side); 0.000 b/h (cold side)
Inlet Temperature
248.4°F (hot side); 135.7°F (cold side)
Outlet Temperature
229.4°F (hot side); 180.0°F (cold side)
Saturated Temperature
248.4°F
Pressure Drop
1.67 psi (hot side); 3.28 psi (cold side)
Operating Pressure - In/Out
29.00 / 27.33 psia
Heat Exchange
1000 kBtu/h (with 1,036 lb/h of steam and 50 US GPM of fluid flow)